1MRS759142 F
7.2.6.2
ESDCSSWI Output signals
Table 1317: ESDCSSWI Output signals
Name
TRV_T_OP_ALM
TRV_T_CL_ALM
OPR_ALM
OPR_LO
MON_ALM
OPENPOS
INVALIDPOS
CLOSEPOS
7.2.7
ESDCSSWI Settings
Table 1318: ESDCSSWI Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Open alarm time
40...30000
Close alarm time
40...30000
Alarm Op number
0...99999
Inactive Alm days
0...9999
Travel time Clc
1=From Cmd to Pos
mode
2=From Pos to Pos
Lockout Op num-
0...99999
ber
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
ms
10
ms
10
1
1
1
Condition monitoring functions
Description
Switch open travel time ex-
ceeded set value
Switch close travel time ex-
ceeded set value
Number of switch operations
exceeds alarm limit
Number of switch operations
exceeds lockout limit
Switch not operated for long
time alarm
Apparatus open position
Apparatus position is invalid
Apparatus closed position
Default
Description
1=on
Operation Off / On
15000
Alarm level setting
for open travel time
in ms
15000
Alarm level setting
for close travel time
in ms
200
Alarm limit for
number of opera-
tions
2000
Alarm limit value of
the inactive days
counter
2=From Pos to Pos
Travel time mode
selection
300
Lock out limit for
number of opera-
tions
1381