underreaching function is connected to the CSUR input. The duration of the CSUR
input signal can be prolonged by the
duration of the CS_PRM signal.
In the permissive overreach scheme, the received signal CR_PRM or CRL, if
the unblocking function is enabled, is used to allow the overreaching residual
overcurrent function DEFLPDEF to trip (activation of the OPERATE output) after the
settable pick-up delay
zone is connected to the CACC input.
The CS_PRM signal is also generated if the CR_PRM signal is received and the local
carrier acceleration signal CACC is active.
Activating the BLOCK input totally blocks the permissive overreach scheme. The
CS_PRM and OPERATE outputs can be blocked by the BLK_CS_OPR input.
Bus A
~
Z2_START
Figure 713: Simplified functional diagram of the permissive overreach scheme
Directional comparison blocking scheme DCB
The directional comparison blocking scheme is enabled with
"Blocking".
In the blocking scheme, the START signal from the reverse-looking residual
overcurrent function DEFLPDEF set to operate for the reverse direction earth fault,
is connected to the CSBLK input to create a CS_BLOCKING signal. The starting of
the reverse-looking function indicates that the fault is located outside the protected
feeder. The duration of the CSBLK input signal can be prolonged with the
Dur setting to ensure a sufficient duration of the CS_BLOCKING signal.
The blocking scheme is mainly used to allow the forward-looking overreaching
residual overcurrent function to trip (activation of the OPERATE output) after the
REX640
Technical Manual
In case of parallel feeders, when the external current reversal logic
(RCRWPSCH) is enabled, the CS_PRM signal is not prolonged and the
Carrier Min Dur is set to zero to secure correct operation.
value of
Coordination time . The start signal from the overreaching
3
CB_A
TRIP_CB_A
Protection related functions
Carrier Min Dur setting to ensure a sufficient
CB_B
DEFL_START
DEFH_START
Bus B
~
3
TRIP_CB_B
Scheme type =
Carrier Min