Protection functions
Load angle2
Load angle1
Figure 586: Mho operation characteristics
The reach of inner circle is defined by the settings
reverse . Angle defined by settings Inner R1 and Inner X1 defines also reverse zone
angle. The reach of outer circle is defined by the settings
X1 reverse . Angle defined by settings Outer R1 and Outer X1 defines also reserve
zone angle.
The PSB and SWING_ST outputs can be blocked by activating BLOCK input. Blocking
also resets internal timers and impedance calculation.
4.7.6.6
Application
Describe different application possibilities of the function. The application
information answers one or more of the following questions:
• The problem of the application
• The purpose of the function
• Solution for the problem in general level
• Where can the function be used?
• When can the function be used?
• The application information shall NOT describe what the user should consider
or should calculate, plan, dimension etc. to make the function work in the
applications.
Power swing detection functions detect power swing conditions by using the fact
that the voltage/current variation during a power swing is slow compared to the
step change during a fault. Both faults and power swings may cause the positive
sequence impedance to enter into the operating characteristic of a distance relay
1050
Inner Rv Ld Ris Rch
X
Outer R1
Outer X1
Inner X1
Inner R1
Outer Fw Ld
Outer Rv Ld
Ris Rch
Inner Fw Ld
Ris Rch
-Outer X1 reverse
Ris Rch
-Inner X1 reverse
Inner R1, Inner X1, Inner X1
Outer R1, Outer X1, Outer
Technical Manual
1MRS759142 F
Load angle1
R
Load angle2
REX640