Advertisement

Protection related functions
Table 1166: Special conditions
Condition
U3P connected to real meas-
urements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
5.8.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of CVPSOF can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
CB_CL_CMD
START_DLYD
Figure 697: Functional module diagram
Trigger
This module is used for detecting a possible fault immediately after circuit breaker
closing. The use of external protection function, typically the start signal from a
1224
START
I_A
I_B
I3P
I_C
U_A
U_B
U3P
U_C
BLOCK
Description
The function can work with any two phase voltage channels
connected but it is recommended to connect all three volt-
age channels.
Trigger
Dead-line
detector
SOTF
detection
1MRS759142 F
Operation setting. The
SOTF
OPERATE
control
Technical Manual