ABB RELION REX640 Technical Manual page 1113

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Figure 625: Inverse-time characteristic curves for overload stage
If the integrated current exceeds 1.1 times the setting
short period but does not operate as the current decreases within
overload , the output ST_OVLOD is kept active but the operation timer is frozen.
However, if the integrated current exceeds 1.1 times the
setting value again, the operation timer continue from the freezing point. Thus, the
operation timer is cumulative. If the integrated current exceeds 1.1 times the setting
Start value overload only once and remains within the Start value overload area for
24 hours, the operation timer and the output ST_OVLOD are reset.
REX640
Technical Manual
Protection functions
Start value overload for a
Start value
Start value overload
1113