ABB RELION REX640 Technical Manual page 1084

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
2=Leading
Start reset Val Dir
1=Lagging
2=Leading
Alarm value Dir
1=Lagging
2=Leading
Alarm reset Val Dir
1=Lagging
2=Leading
Start value
-0.99...0.99
Start reset value
-0.99...0.99
Alarm value
-0.99...0.99
Alarm reset value
-0.99...0.99
Operate delay time
100...300000
Alarm delay time
100...300000
Table 1023: MPUPF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Min operate current 0.05...0.65
Min operate volt-
0.05...0.50
age
Disable time
0...60000
Voltage reversal
0=No
1=Yes
Table 1024: MPUPF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.8.4.9
MPUPF Monitored data
Table 1025: MPUPF Monitored data
Name
Type
START_DUR
FLOAT32
PF
FLOAT32
MPUPF
Enum
1084
Unit
Step
0.01
0.01
0.01
0.01
ms
1
ms
1
Unit
Step
xIn
0.01
xUn
0.01
ms
1
Unit
Step
ms
1
Values (Range)
0.00...100.00
-1.00...1.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Default
1=Lagging
1=Lagging
1=Lagging
0.80
0.85
0.85
0.90
500
500
Default
1=on
0.10
0.10
5000
0=No
Default
20
Unit
Description
%
Ratio of start time / op-
erate time
Calculated value of the
3-phase power factor
Status
1MRS759142 F
Description
PF direction for
start reset value
PF direction for
alarm value
PF direction for
alarm reset value
Start value
Value at which start
resets, drops out
Alarm start value
Value at which
alarm resets, drops
out
Time delay for op-
eration
Time delay for
alarm
Description
Operation Off / On
Minimum operating
current
Minimum operating
voltage
Additional wait
time after CB clos-
ing
Rotates the PF by
180 degrees
Description
Reset delay time
REX640
Technical Manual