The recording always contains all binary channels of the disturbance recorder. If one
of the binary channels is disabled, the recorded state of the channel is continuously
FALSE and the state changes of the corresponding channel are not recorded.
The corresponding channel name for disabled binary channels in the COMTRADE
configuration file is Unused BI.
To enable or disable an analog or a binary channel of the disturbance recorder, the
Operation parameter of the corresponding analog or binary channel is set to "on" or
"off".
The states of manual triggering and periodic triggering are not included in the
recording, but they create a state change to the
triggering status parameters, which in turn create events.
The TRIGGERED output can be used to control the indication LEDs of the protection
relay. The triggering of the disturbance recorder sets the TRIGGERED output to
TRUE. The output remains in this state until all the data for the corresponding
recording has been recorded.
8.2.5
Application
The disturbance recorder is used for post-fault analysis and for verifying the correct
operation of protection relays and circuit breakers. It can record both analog and
binary signal information. The analog inputs are recorded as instantaneous values
and converted to primary peak value units when the protection relay converts the
recordings to the COMTRADE format.
The binary channels are sampled once per task execution of the disturbance
recorder. The task execution interval for the disturbance recorder is the same as
for the protection functions. During the COMTRADE conversion, the digital status
values are repeated so that the sampling frequencies of the analog and binary
channels correspond to each other. This is required by the COMTRADE standard.
8.2.6
Signals
Table 1438: RDRE Output signals
Name
TRIGGERED
8.2.7
Settings
REX640
Technical Manual
The IP number of the protection relay and the value of the
parameter are both included in the COMTRADE configuration file for
identification purposes.
COMTRADE is the general standard format used for storing disturbance
recordings.
The disturbance recorder follows the 1999 version of the COMTRADE
standard and uses the binary data file format.
Type
BOOLEAN
Measurement functions
Periodic triggering and Manual
Bay name
Description
Recording started
1493