Protection functions
Figure 560: Operating region for out of step with double blinder
A third zone, Zone 3, can be enabled by setting
defined to include the area outside of the circular mho characteristic but inside the
area that is bound with the magnitude of the minimum positive-sequence current
defined by setting
determine the shape of the zones should be coordinated with the settings for
any distance protection functions. The zones and their respective slip counters are
applicable only for Way out operations when the
is "Way out" or "Adaptive".
1008
An impedance is only considered to be within the mho circle if it is also
between the inner blinders.
Min Ps Seq .
Figure 561
Zone 3 enable to "Yes". Zone 3 is
shows the three zones. Settings that
Oos operation mode setting option
1MRS759142 F
REX640
Technical Manual