ABB RELION REX640 Technical Manual page 1184

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
Name
Type
PHIZ
Enum
5.5
Binary signal transfer BSTGAPC (ANSI BST)
5.5.1
Identification
Function description
Binary signal transfer
5.5.2
Function block
Figure 676: Function block
5.5.3
Functionality
The binary signal transfer function BSTGAPC is used for transferring binary signals
between the local and remote end line differential protection relays. The function
includes eight binary signals that are transferred in the protection communication
telegram and can be freely configured and used for any purpose in the line
differential application.
BSTGAPC transfers binary data continuously over the protection communication
channel between the terminals. Each of the eight signals are bidirectional and the
binary data sent locally is available remotely as a received signal.
BSTGAPC includes a minimum pulse time functionality for the received binary
signals. Each received signal has its own minimum pulse time setting parameter.
1184
Values (Range)
Unit
1=open
2=closed
3=faulty
1=on
2=blocked
3=test
4=test/blocked
5=off
IEC 61850
identification
BSTGAPC
1MRS759142 F
Description
Status
IEC 60617
ANSI/IEEE C37.2
identification
device number
BST
BST
Technical Manual
REX640

Advertisement

Table of Contents
loading