Directional detector
The Directional detector module compares the angle of the positive-sequence
current I1 to the angle of the positive-sequence voltage V1. Using the positive-
sequence voltage angle as reference, the positive-sequence current angle is
compared to the
operating sector selected with the
Timer.
The operating sector is defined by the setting
angle , Min reverse angle and Max reverse angle . The options that can be selected for
the
Low-level blocking
For a reliable operation, signal levels should be greater than the minimum level.
If they are not greater than the minimum level, Timer is blocked. If the amplitude
of the positive-sequence current is greater than the
positive-sequence voltage amplitude is greater than the
On signal is sent to Timer.
Timer
Once activated, the internal operating timer is started. The Timer characteristic is
according to definite time DT. When Timer has reached the value of
time , the RELEASE output is activated. If a drop-off situation happens, that is, if
the operating current moves outside the operating sector or signal amplitudes drop
REX640
Technical Manual
I3P
U3P
BLOCK
Characteristic angle setting. If the angular difference is within the
Directional mode setting are "Forward" and "Reverse".
The sector limits are always given as positive degree values.
Characteristic angle setting is also known as Relay Characteristic
The
Angle (RCA), Relay Base Angle or Maximum Torque Line.
I
1
Directional
detector
U
1
Low level
blocking
Blocking
logic
Directional mode setting, the On signal is sent to
Min forward angle , Max forward
Protection related functions
DIRECTION
Timer
t
RELEASE
Min trip current value and the
Min trip voltage value, the
Release delay
1283