ABB RELION REX640 Technical Manual page 1017

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.7.3.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of UEXPDIS can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
EXT_LOS_DET
Figure 564: Functional module diagram
Impedance calculation
This module calculates the apparent impedance based on the selected voltages
and currents. The
which voltages and currents are to be used. If the
"1Phase-earth" or "1Phase-phase", the
determining which phase or phase-phase voltages ("A or AB", "B or BC" and "C or
CA") and currents should be used for calculating the impedance.
Table 947: Voltages and currents used in impedance calculation
Measurement mode
1Phase-earth
1Phase-earth
1Phase-earth
1Phase-phase
1Phase-phase
1Phase-phase
3Phase-earth
Table continues on the next page
REX640
Technical Manual
I_A
I_B
I3P
I_C
I
1
U_A_AB
U_B_BC
U3P
U_C_CA
U
1
BLOCK
Measurement mode and Phase Sel for Z Clc settings determine
Phase Sel for Z Clc
A or AB
B or BC
C or CA
A or AB
B or BC
C or CA
N/A
Operation setting. The
Impedance
reach check
Impedance
calculation
External
loss
detection
Blocking
logic
Measurement mode is set to
Phase Sel for Z Clc setting is needed for
Voltages and currents
U_A, I_A
U_B, I_B
U_C, I_C
U_AB, I_A, I_B
U_BC, I_B, I_C
U_CA, I_C, I_A
U_A, U_B, U_C, I_A, I_B, I_C
Protection functions
Timer
OPERATE
t
START
1017