4.7.3.9
UEXPDIS Monitored data
Table 955: UEXPDIS Monitored data
Name
Type
START_DUR
FLOAT32
Z_AMPL_A
FLOAT32
Z_ANGLE_A
FLOAT32
Z_AMPL_B
FLOAT32
Z_ANGLE_B
FLOAT32
Z_AMPL_C
FLOAT32
Z_ANGLE_C
FLOAT32
Z_AMPL_AB
FLOAT32
Z_ANGLE_AB
FLOAT32
Z_AMPL_BC
FLOAT32
Z_ANGLE_BC
FLOAT32
Z_AMPL_CA
FLOAT32
Z_ANGLE_CA
FLOAT32
Z1_AMPL
FLOAT32
Z1_ANGLE
FLOAT32
UEXPDIS
Enum
4.7.3.10
Technical data
Table 956: UEXPDIS Technical data
Characteristic
Operation accuracy
Start time
Reset time
Table continues on the next page
1
f
= 50Hz, results based on statistical distribution of 1000 measurements
n
2
Includes the delay of the signal output contact
REX640
Technical Manual
Values (Range)
0.00...100.00
0.00...200.00
-180.00...180.00
0.00...200.00
-180.00...180.00
0.00...200.00
-180.00...180.00
0.00...200.00
-180.00...180.00
0.00...200.00
-180.00...180.00
0.00...200.00
-180.00...180.00
0.00...200.00
-180.00...180.00
1=on
2=blocked
3=test
4=test/blocked
5=off
1, 2
Protection functions
Unit
Description
%
Ratio of start time / op-
erate time (in %)
xZn
Impedance amplitude
phase A
deg
Impedance angle phase
A
xZn
Impedance amplitude
phase B
deg
Impedance angle phase
B
xZn
Impedance amplitude
phase C
deg
Impedance angle phase
C
xZn
Phase-to-phase A-B im-
pedance amplitude
deg
Phase-to-phase A-B im-
pedance phase angle
xZn
Phase-to-phase B-C im-
pedance amplitude
deg
Phase-to-phase B-C im-
pedance phase angle
xZn
Phase-to-phase C-A im-
pedance amplitude
deg
Phase-to-phase C-A im-
pedance phase angle
xZn
Positive sequence im-
pedance amplitude
deg
Positive sequence im-
pedance phase angle
Status
Value
Depending on the frequency of the meas-
ured current and voltage:
f = f
± 2 Hz
n
±3.0% of the set value or ±0.2% Zb