ABB RELION REX640 Technical Manual page 1018

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Measurement mode
3Phase-phase
Pos seqn
If the polarity of the voltage signals is opposite to the normal polarity, the
correction can be done by setting
impedance vector by 180 degrees.
If the magnitude of the voltage is less than 0.05 · U
is not reliable and the impedance calculation is disabled. U
phase voltage.
The calculated impedance magnitudes and angles are available in the Monitored
data view. The impedance angles are provided between -180...180 degrees.
Impedance reach check
The operating characteristic is a circular offset mho on the impedance plane. The
operating characteristics are defined with the
settings. If the calculated impedance value enters the circle in the impedance plane,
the module sends an enabling signal to start the Timer.
1018
Phase Sel for Z Clc
N/A
N/A
If all three phase voltages and phase currents are fed to the protection
relay, the positive-sequence alternative is recommended.
The calculated apparent impedance is converted to pu impedance as the
operating characteristics are defined with the pu settings.
Voltages and currents
U_AB, U_BC, U_CA, I_A, I_B, I_C
{ U_A,U_B,U_C } or { U_AB,U_BC,U_CA } and
I_A, I_B, I_C
Voltage reversal to "Yes", which rotates the
, the calculated impedance
N
Offset , Diameter and Displacement
1MRS759142 F
is the rated phase-to-
N
REX640
Technical Manual