ABB RELION REX640 Technical Manual page 1106

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.11.2
Function block
Figure 620: Function block
4.11.3
Functionality
The multipurpose protection function MAPGAPC is used as a general protection
with many possible application areas as it has flexible measuring and setting
facilities. The function can be used as an under- or overprotection with a settable
absolute hysteresis limit. The function operates with the definite time (DT)
characteristics.
The function contains a blocking functionality. It is possible to block function
outputs, the definite timer or the function itself.
4.11.4
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of MAPGAPC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 621: Functional module diagram
Level detector
The level detector compares AI_VALUE to the
mode setting defines the direction of the level detector.
1106
AI_VALUE
ENA_ADD
BLOCK
Operation setting. The
Timer
Level
t
detector
Blocking
logic
Start value setting. The Operation
1MRS759142 F
OPERATE
START
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents