Protection functions
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
Check the contents of this chapter and also the preprocessing blocks in this
document. The configuration can be written to the protection relay once the
mismatch is corrected.
4.12.5.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "on" and "off".
The operation of CNUPTOV can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 642: Functional module diagram
Natural unbalance compensation
This module calculates the natural unbalance compensation. Calculation for
compensation is initiated through the command Record unbalance, available under
the menu path Control > CNUPTOV. The function equates the operating signal to
zero and calculates
U
unb
For more information, see the
manual.
If the positive-sequence voltage is available at the time of memorizing the
value, the positive-sequence voltage is also memorized as
applies the revised compensation voltage to account for change in bus voltages
between the moment of memorizing the compensation voltage and the time of
applying it.
U
unb
Figure 643: Equation
1150
U_A
U_B
U3P
U_C
U
1
U
o
URES
U
neutral
UNEUT
BLOCK
U
from the available known quantities.
unb
( )
m
. This memorized value is then used when calculating the operating quantity.
U
1
U
( )
m
=
unb
U m
( )
1
Operation setting. The
Natural
unbalance
Level
compensati
detector
on
Blocking
logic
Chapter 4.12.5.6 Operating quantity
1MRS759142 F
Timer
OPERATE
t
START
U
is memorized as
unb
section in this
U
unb
U m
( )
. The function then
1
REX640
Technical Manual
( )
m