ABB RELION REX640 Technical Manual page 1484

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Measurement functions
Parameter
Values (Range)
5=off
Power unit Mult
3=k
6=M
Energy unit Mult
3=k
6=M
Active power Dir
1=Forward
2=Reverse
Reactive power Dir
1=Forward
2=Reverse
Power deadband
1000...10000
Pulse quantity
1...10000000
Table 1434: PEMMXU Non group settings (Advanced)
Parameter
Values (Range)
Forward Wh Initial
0...999999999
Reverse Wh Initial
0...999999999
Forward VArh Initial 0...999999999
Reverse VArh Initial
0...999999999
Measurement
1=PhsA, PhsB, PhsC
mode
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Pulse on time
0.050...60.000
Pulse off time
0.050...60.000
8.1.13.7
PEMMXU Monitored data
1484
Unit
Step
1
Wh/VArh
1
Unit
Step
1
1
1
1
s
0.001
s
0.001
1MRS759142 F
Default
Description
3=k
Unit multiplier for
presentation of the
power related val-
ues
3=k
Unit multiplier for
presentation of the
energy related val-
ues
1=Forward
Direction of active
power flow: For-
ward, Reverse
1=Forward
Direction of reac-
tive power flow:
Forward, Reverse
10000
Deadband configu-
ration value for in-
tegral calculation.
(percentage of Sn
as 0,001 % s)
100000
Pulse quantity for
the energy pulse
outputs
Default
Description
0
Preset Initial value
for forward active
energy
0
Preset Initial value
for reverse active
energy
0
Preset Initial value
for forward reactive
energy
0
Preset Initial value
for reverse reactive
energy
1=PhsA, PhsB, PhsC Selected measure-
ment mode for
power calculation
1.000
Energy accumula-
ted pulse ON time
in secs
0.500
Energy accumula-
ted pulse OFF time
in secs
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents