ABB RELION REX640 Technical Manual page 1323

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
In the example, the incoming feeder is carrying a load of 2.0 pu and both outgoing
feeders carry an equal load of 1.0 pu However, both HIxPDIF and HZCCxSPVC
consider the current as an increased differential or unbalance current because of
the broken CT wire in phase C. Both HIxPDIF and HZCCxSPVC receive the differential
current of approximately 1.0 pu The main differential protection HIxPDIF cannot
operate because of the higher current setting.
The ALARM output of the CT supervision function can be used to energize an
auxiliary relay which can short-circuit the current CT wires, making the busbar
differential protection inoperative. This arrangement does not prevent unwanted
operation of HIxPDIF if the start setting is below the rated load. For example, if
the start setting for HIxPDIF in the example is set as 0.8 pu HIxPDIF operate before
HZCCxSPVC.
6.3.8
Signals
6.3.8.1
HZCCASPVC Input signals
Table 1254: HZCCASPVC Input signals
Name
I3P
BLOCK
6.3.8.2
HZCCBSPVC Input signals
Table 1255: HZCCBSPVC Input signals
Name
I3P
BLOCK
6.3.8.3
HZCCCSPVC Input signals
Table 1256: HZCCCSPVC Input signals
Name
I3P
BLOCK
REX640
Technical Manual
All CTs must have the same ratio.
Type
SIGNAL
BOOLEAN
Type
SIGNAL
BOOLEAN
Type
SIGNAL
BOOLEAN
Supervision functions
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating blocking mode
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating blocking mode
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating blocking mode
1323

Advertisement

Table of Contents
loading

Table of Contents