ABB RELION REX640 Technical Manual page 1374

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Condition monitoring functions
Parameter
Values (Range)
Alarm Op number
0...99999
Lockout Op num-
0...99999
ber
Current exponent
0.00...5.00
Difference Cor time -10...10
Alm Acc currents
0.00...20000.00
Pwr
LO Acc currents
0.00...20000.00
Pwr
Initial CB Rmn life
0...99999
Rated Op current
100.00...6300.00
Rated fault current
500.00...99999.00
Op number rated
1...99999
Op number fault
1...10000
Inactive Alm days
0...9999
Travel time Clc
1=From Cmd to Pos
mode
2=From Pos to Pos
Table 1313: SSCBR Non group settings (Advanced)
Parameter
Values (Range)
Opening time Cor
-100...100
Closing time Cor
-100...100
Counter initial Val
0...99999
Ini Acc currents Pwr 0.00...20000.00
Life alarm level
0...99999
Pressure alarm
0...60000
time
Pres lockout time
0...60000
Ini inactive days
0...9999
Inactive Alm hours
0...23
1374
Unit
Step
1
1
0.01
ms
1
0.01
0.01
1
A
0.01
A
0.01
1
1
1
Unit
Step
ms
1
ms
1
1
0.01
1
ms
1
ms
10
1
h
1
1MRS759142 F
Default
Description
200
Alarm limit for
number of opera-
tions
300
Lock out limit for
number of opera-
tions
2.00
Current exponent
setting for energy
calculation
5
Corr. factor for
time dif in aux. and
main contacts open
time
2500.00
Setting of alarm
level for accumula-
ted currents power
2500.00
Lockout limit set-
ting for accumula-
ted currents power
5000
Initial value for the
CB remaining life
1000.00
Rated operating
current of the
breaker
5000.00
Rated fault current
of the breaker
10000
Number of opera-
tions possible at
rated current
1000
Number of opera-
tions possible at
rated fault current
2000
Alarm limit value of
the inactive days
counter
2=From Pos to Pos
Travel time calcu-
lation mode selec-
tion
Default
Description
10
Correction factor
for open travel time
in ms
10
Correction factor
for CB close travel
time in ms
0
The operation num-
bers counter initial-
ization value
0.00
Initial value for ac-
cumulation energy
(Iyt)
500
Alarm level for CB
remaining life
10
Time delay for gas
pressure alarm in
ms
10
Time delay for gas
pressure lockout in
ms
0
Initial value of the
inactive days coun-
ter
0
Alarm time of the
inactive days coun-
ter in hours
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents