ABB RELION REX640 Technical Manual page 1083

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
There are two general applications which can best utilize under power factor
protection; power-factor control and loss of excitation.
When applying the function for power-factor control, both the start value and the
start reset value should be the same sign (positive/negative) as well as the same
direction (leading/lagging). Additionally, the absolute value of the start reset value
should be greater than or equal to the absolute value of the start value. This allows
the function to properly control any power factor controls within the system.
When applying the function for loss of excitation, both the start value and the start
reset value should be the same sign (positive/negative), but the directions should
be different (leading/lagging). This application is well-suited to protect against
back-spinning. In this case the start reset value will only come into play once the
system provides power in the opposite quadrant of the start value, for example,
lagging PF turns to leading PF.
4.8.4.7
Signals
MPUPF Input signals
Table 1020: MPUPF Input signals
Name
I3P
U3P
BLOCK
DISABLE
MPUPF Output signals
Table 1021: MPUPF Output signals
Name
OPERATE
START
ALARM
4.8.4.8
MPUPF Settings
Table 1022: MPUPF Group settings (Basic)
Parameter
Values (Range)
Start value Dir
1=Lagging
Table continues on the next page
REX640
Technical Manual
Type
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
Protection functions
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
0=False
Signal to block the
function during ma-
chine startup
Description
Operate
Start
Alarm
Default
1=Lagging
Description
PF direction for
start value
1083