ABB RELION REX640 Technical Manual page 1162

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
Characteristic
Reset time
Reset ratio
Operate time accuracy
5.2
Circuit breaker failure protection CCBRBRF (ANSI
50BF)
5.2.1
Identification
Function description
Circuit breaker failure protection
5.2.2
Function block
Figure 659: Function block
5.2.3
Functionality
The circuit breaker failure protection function CCBRBRF is activated by trip
commands from the protection functions. The commands are either internal
commands to the terminal or external commands through binary inputs. The
start command is always a default for three-phase operation. CCBRBRF includes
a three-phase conditional or unconditional retrip function, and also a three-phase
conditional back-up trip function.
CCBRBRF uses the same levels of current detection for both retrip and back-up
trip. The operating values of the current measuring elements can be set within
a predefined setting range. The function has two independent timers for trip
purposes: a retrip timer for the repeated tripping of its own breaker and a back-up
timer for the trip logic operation for upstream breakers. A minimum trip pulse
length can be set independently for the trip output.
1162
Value
±1.5 % of the set value or ±0.002 × I
Ratio I2f/I1f measurement:
±5.0 % of the set value
+35 ms / -0 ms
Typically 0.96
+35 ms / -0 ms
IEC 61850
IEC 60617
identification
identification
CCBRBRF
3I>/Io>BF
1MRS759142 F
n
ANSI/IEEE C37.2
device number
50BF
REX640
Technical Manual