Condition monitoring functions
7.4
Cable fault detection RCFD (ANSI CFD)
7.4.1
Identification
Function description
Cable fault detection
7.4.2
Function block
Figure 793: Function block
7.4.3
Functionality
The self-clearing fault detection function (RCFD) calculates half cycle DFT of the
current signal for all the three phases and earth and uses it to detect a self-clearing
fault pronounced primarily in cable networks.
The function provides individual counter values for number of times a self-clearing
fault is observed in each phase and earth. The function determines the self-clearing
fault is detected in all three phases or earth.
7.4.4
Analog input configuration
RCFD has two analog group inputs which must be properly configured.
Table 1332: Analog inputs
Input
I3P
IRES
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
1398
Description
Three-phase currents.
Measured residual current
See the preprocessing function blocks in this document for the possible
signal sources.
IEC 61850
IEC 60617
identification
identification
RCFD
CFD
1MRS759142 F
ANSI/IEEE C37.2
device number
CFD
REX640
Technical Manual