ABB RELION REX640 Technical Manual page 1115

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Under current detector
The Under current detector module can be enabled by setting
to "Enable" and disabled by setting it to "Disable". The Under current detector
module is also disabled when CB_CLOSED is FALSE, that is, when circuit breaker is
open.
The fundamental frequency component of phase currents is compared to the
setting
value Un Cur , the Under current detector module enables the Timer 3 module.
Timer 3
Once activated, the Timer 3 module activates the ST_UN_I output. The operation is
based on DT characteristics. When the operation timer has reached the value of
Cur delay time , the OPR_UN_I output is activated.
If the undercurrent situation disappears, the operation timer is reset. The
ST_DUR_UN_I output indicates the percentage ratio of the undercurrent start
situation and the set operation time in the Timer 3 module and is available in the
monitored data view.
The OPR_UN_I output is of pulse type and remains TRUE for 150 ms. After that,
ST_DUR_UN_I and OPR_UN_I are deactivated and ST_DUR_UN_I is reset.
Inhibit reclose
When the output OPR_UN_I becomes active or when the CB_CLOSED state changes
from TRUE to FALSE, that is, when circuit breaker opens, the reclosing inhibition
module activates output BLK_CLOSE.
When the relay powers up after a reboot or software reset, or if the Operation of
COLPTOC function is switched from off to on, the BLK_CLOSE output is activated
defined by the
The behavior of the BLK_CLOSE output depends on
inhibit mode is set to "Lockout", the BLK_CLOSE output needs to be reset manually
from the clearing menu parameter
set to "Non-latched", the BLK_CLOSE output resets after the set
has elapsed.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the BLOCK input and the global setting Configuration > System >
REX640
Technical Manual
CB_CLOSED signal. The CB_CLOSED signal is True when the CB position
is closed.
Start value Un Cur . If all the three-phase currents are below the setting Start
If the circuit breaker closed status signal is not detected, the constant
value TRUE has to be connected to CB_CLOSED input to enable the
undercurrent detector.
If the circuit breaker status signal is not connected to CB_CLOSED input,
the OPR_UN_I output is activated even if the circuit breaker is open and
undercurrent is detected.
Enable under current is set to "Disable", the reclosing inhibition
If
operation is based purely on the CB_CLOSED input.
Reclose inhibit time , regardless the Reclose inhibit mode .
Reclose inhibit mode . If Reclose
COLPTOC inhibit recl . If Reclose inhibit mode is
Protection functions
Enable under current
Un
Reclose inhibit time
1115

Advertisement

Table of Contents
loading

Table of Contents