Protection functions
4.7.3.8
UEXPDIS Settings
Table 951: UEXPDIS Group settings (Basic)
Parameter
Values (Range)
Diameter
1...6000
Offset
-1000...1000
Displacement
-1000...1000
Operate delay time
60...200000
Table 952: UEXPDIS Group settings (Advanced)
Parameter
Values (Range)
Restraint enable
0=Disable
1=Enable
Rst offset X
-1000...1000
Rst offset X angle
-180.0...180.0
Table 953: UEXPDIS Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
External Los Det
0=Disable
Ena
1=Enable
Voltage reversal
0=No
1=Yes
Impedance Meas
1=1Phase-to-earth
mode
2=1Phase-to-phase
3=3Phase-to-earth
4=3Phase-to-phase
5=Pos sequence
Phase Sel for Z Clc
1=A or AB
2=B or BC
3=C or CA
Table 954: UEXPDIS Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
1024
Unit
Step
%Zn
1
%Zn
1
%Zn
1
ms
10
Unit
Step
%Zn
1
deg
0.1
Unit
Step
Unit
Step
ms
10
1MRS759142 F
Default
Description
200
Diameter of the
Mho diagram
-10
Offset of top of
the impedance cir-
cle from the R-axis
0
Displacement of
impedance circle
centre from the X-
axis
5000
Operate delay time
Default
Description
0=Disable
Enable restrain
area
0
Offset of direction-
al line from origin
along X-axis
-13.0
Angle between R-
axis and directional
line
Default
Description
1=on
Operation Off / On
1=Enable
Enable external ex-
citation loss detec-
tion
0=No
Rotate voltage sig-
nals by 180 degrees
5=Pos sequence
Select voltage and
currents for impe-
dance calculation
1=A or AB
Voltage phase se-
lection
Default
Description
3000
Reset delay time
Technical Manual
REX640