Measurement functions
Name
Type
BLOCK
BOOLEAN
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
I_INST_A
FLOAT32
I_ANGL_A
FLOAT32
I_DB_A
FLOAT32
I_DMD_A
FLOAT32
I_RANGE_A
Enum
I_INST_B
FLOAT32
I_ANGL_B
FLOAT32
I_DB_B
FLOAT32
I_DMD_B
FLOAT32
I_RANGE_B
Enum
I_INST_C
FLOAT32
I_ANGL_C
FLOAT32
I_DB_C
FLOAT32
I_DMD_C
FLOAT32
I_RANGE_C
Enum
1446
Values (Range)
Unit
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
1MRS759142 F
Description
Block signal for all bina-
ry outputs
High alarm
High warning
Low warning
Low alarm
IL1 Amplitude, magni-
tude of instantaneous
value
IL1 current angle
IL1 Amplitude, magni-
tude of deadband value
Demand value of IL1
current
IL1 Amplitude range
IL2 Amplitude, magni-
tude of instantaneous
value
IL2 current angle
IL2 Amplitude, magni-
tude of deadband value
Demand value of IL2
current
IL2 Amplitude range
IL3 Amplitude, magni-
tude of instantaneous
value
IL3 current angle
IL3 Amplitude, magni-
tude of deadband value
Demand value of IL3
current
IL3 Amplitude range
REX640