1MRS759142 F
Table 1148: Special conditions
Condition
U3P connected to real meas-
urements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
5.7.5
Operation principle
The function can be enabled or disabled with the
corresponding parameter values are "on" and "off".
The operation of SCEFRFLO can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
TRIGG_REC
TRIGG_XC0F
Figure 682: Functional module diagram
The fault distance calculation is done in two steps. First, the fault type is
determined with the in-built Phase selection logic (PSL). Second, based on the
selected impedance measuring element (fault loop) the fault distance from the
measuring point to the fault location is calculated.
The phase current magnitude's minimum threshold value is 1 % xIn.
REX640
Technical Manual
I_A
I_B
I3P
I_C
U_A_AB
U_B_BC
U3P
U_C_CA
U
U
U
URES
TRIGG_T
BLOCK
Description
The function can work with any two phase voltage channels
connected but it is recommended to connect all three volt-
age channels.
Phase
selection
logic
Trigger
1
detection
2
0
Protection related functions
Operation setting. The
Fault
impedance
and
distance
calculation
Alarm
indication
ALARM
Recorded
data
1195