Protection related functions
Name
CRL
LCG
5.11.7
RESCPSCH Settings
Table 1193: RESCPSCH Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Scheme type
1=None
2=Intertrip
3=Permissive Un-
derreach
4=Permissive Over-
reach
5=Blocking
Carrier Min Dur
0...60000
Coordination time
0...60000
Table 1194: RESCPSCH Non group settings (Advanced)
Parameter
Values (Range)
Unblock mode
1=Off
2=Permanent
3=Time window
Loss of carrier time 0...60000
5.11.8
RESCPSCH Monitored data
Table 1195: RESCPSCH Monitored data
Name
Type
RESCPSCH
Enum
1264
Type
BOOLEAN
BOOLEAN
Unit
Step
ms
1
ms
1
Unit
Step
ms
1
Values (Range)
1=on
2=blocked
3=test
4=test/blocked
5=off
Description
Carrier received after unblock
logic
Loss of guard
Default
1=on
3=Permissive Un-
derreach
100
35
Default
1=Off
35
Unit
Description
Status
1MRS759142 F
Description
Operation Off / On
Scheme type, mode
of operation
Minimum duration
of carrier send sig-
nal
Co-ordination tim-
er for blocking
scheme
Description
Unblock function
mode for scheme
type
Pickup security
timer on loss of
carrier guard signal