Characteristic
Max torque line
Figure 730: Configurable directional setting when "Neg. seq. volt." selection is made
using the Pol quantity setting
When
directional detector module compares the angle of the residual current to the
residual voltage. Using the residual voltage as reference, the residual current angle
is compared to the
operating sector selected by the
to Timer.
REX640
Technical Manual
-U
RCA=+45 deg
Angle/
Max
forward
angle
I
2
Min
Forward
forward
angle
area
Min operate
current
Zero seq. volt. voltage selection is made using Pol quantity setting, the
Characteristic angle setting. If the angle difference is within the
The polarizing quantity (residual voltage) is inverted because of switched
voltage measurement cables, the correction can be done by setting the
Pol reversal setting to "True", which rotates the polarizing quantity by 180
degrees.
The directional characteristic for the measured or calculated residual
power is same.
2
Zero torque line
Backward
Min
area
reverse
angle
Min operate
voltage
Max
reverse
angle
Directional mode setting, the Enable signal is sent
Protection related functions