ABB RELION REX640 Technical Manual page 1229

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
Current dead Lin
0.01...1.00
Val
Voltage dead Lin
0.01...0.58
Val
Cur voltage Det
0...60000
time
Operate time delay
0...120000
SOTF reset time
0...60000
Dead line time
0...60000
5.8.9
CVPSOF Monitored data
Table 1173: CVPSOF Monitored data
Name
Type
CVPSOF
Enum
REX640
Technical Manual
Unit
Step
xIn
0.01
xUn
0.01
ms
10
ms
10
ms
10
ms
10
Values (Range)
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection related functions
Default
0.20
0.40
20
20
1000
200
Unit
Description
Status
Description
Dead line value,
current. Used also
in auto activation
logic
Dead line value,
voltage. Used also
in auto activation
logic
Time delay for volt-
age and current
based detection
Delay for the de-
layed start input
SOTF detection pe-
riod after initializa-
tion
Delay time for acti-
vation of dead line
detection
1229

Advertisement

Table of Contents
loading

Table of Contents