Protection functions
Steps to measure natural unbalance current
1.
2.
3.
4.
5.
4.12.2.7
Signals
CUBPTOC Input signals
Table 1068: CUBPTOC Input signals
Name
IUNB
I3P
BLOCK
CUBPTOC Output signals
Table 1069: CUBPTOC Output signals
Name
OPERATE
START
ALARM
4.12.2.8
CUBPTOC Settings
Table 1070: CUBPTOC Group settings (Basic)
Parameter
Values (Range)
Alarm mode
1=Normal
Table continues on the next page
1128
Connect the phase current analog input I_A and unbalance current
I_UNB to the protection relay for the CUBPTOC function to start working.
Natural Comp Enable must be set to "TRUE".
The setting
The capacitor bank must be energized.
The capacitor bank compensated unbalance current I_COM_AMPL is observed
from Monitored data.
Record unbalance must be activated by selecting the
The command
value "Record" which stores the unbalance reference for future unbalance
calculations.
The compensated unbalance current ( I_COM_AMPL) is re-checked to be
approximately zero.
The natural unbalance recording should be made only during the steady-
state condition and when all the capacitor bank elements are assumed to
be in service.
Type
SIGNAL
SIGNAL
BOOLEAN
Unit
Default
-
-
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
Step
1MRS759142 F
Description
Analog input
Three-phase currents
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Alarm
Default
Description
1=Normal
Mode of operation
for Alarm stage
Technical Manual