ABB RELION REX640 Technical Manual page 1072

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.8.3
Directional reactive power undervoltage protection
DQPTUV (ANSI 32Q,27)
4.8.3.1
Identification
Function description
Directional reactive power under-
voltage protection
4.8.3.2
Function block
Figure 598: Function block
4.8.3.3
Functionality
The directional reactive power undervoltage protection function DQPTUV is used at
the grid connection point of distributed power generating units as stipulated by
various grid codes to prevent voltage collapse of the grid due to network faults.
DQPTUV measures phase voltages and current at the grid connection point. The
generating facility is disconnected from the network with a specific time delay if all
phase voltages decrease and remain at or below the specified limit and if reactive
power is simultaneously consumed (that is, under-excitation operation).
DQPTUV contains a blocking functionality to block function outputs, timer or the
function itself.
4.8.3.4
Analog channel configuration
DQPTUV has two analog group inputs which must be properly configured.
Table 1009: Analog inputs
Input
I3P
U3P
There are a few special conditions which must be noted with the configuration.
1072
Description
Three-phase currents
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
IEC 61850
IEC 60617
identification
identification
DQPTUV
Q> ->,3U<
1MRS759142 F
ANSI/IEEE C37.2
device number
32Q,27
REX640
Technical Manual