ABB RELION REX640 Technical Manual page 1011

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
f
slip
f
slip
δ
0
VoltagedipTm
Otherwise, OPERATE is activated on the way out, when the impedance exits an outer
blinder and the swing repeats for the set
enabled zone that the swing has passed through.
If the
continues through the opposite blinders without passing through the mho circle,
the SWING output is activated. The SWING output remains activated for a time
determined by the
time expires causing the output to remain active for another
this swing is repeated for the set
setting is "Yes", the SWING_OP output is activated. The SWING_OP output remains
activated for a time determined by the
If the "Adaptive" option is selected and an OSB condition is not detected, but
the impedance enters the mho circle after remaining between the inner and outer
blinders for greater than 1.5 cycles, the function assumes a severe swing and assert
the OPERATE output.
The drop out delay for OPERATE output can be set by
If the polarity of the voltage signal is opposite to the normal polarity, the correction
can be done by setting
vector by 180 degrees.
The DISABLE input can be used to coordinate the correct operation during the
start-up situation. The function is blocked by activating the DISABLE signal. Once
the DISABLE signal is deactivated, the function remains blocked (outputs disabled)
for additional time duration as set through the setting
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the BLOCK input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The BLOCK input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the BLOCK signal activation
is preselected with the global setting
The
mode, the operation timer is frozen to the prevailing value, but the OPERATE output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the OPERATE output is not activated.
REX640
Technical Manual
π δ
(
)
0
π
VoltagedipTm
Slip frequency
Swing angle at the outer blinder
Set
V dip time
Swing time has elapsed but the impedance exits the inner blinder and
Reset time setting unless another swing occurs before the reset
Voltage reversal to "Yes", which rotates the impedance
Blocking mode setting has three blocking methods. In the "Freeze timers"
Max number slips count in the respective
Max Num slips Zn3 count and the Zone 3 enable
Operate dropout time setting.
Operate dropout time setting.
Disable time .
Blocking mode .
Protection functions
(Equation 275)
Reset time interval. If
1011