Measurement functions
CMMXU Input signals
Table 1363: CMMXU Input signals
Name
I3P
BLOCK
CMMXU Output signals
Table 1364: CMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
I_INST_A
I_INST_B
I_INST_C
I_DMD_A
I_DMD_B
I_DMD_C
8.1.4.6
CMMXU Non group settings
Table 1365: CMMXU Non group settings (Basic)
Parameter
Values (Range)
Operation
Num of phases
A high high limit
0.00...40.00
A high limit
0.00...40.00
A low limit
0.00...40.00
Table continues on the next page
1444
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
FLOAT32
FLOAT32
FLOAT32
FLOAT32
FLOAT32
FLOAT32
Unit
Step
xIn
0.01
xIn
0.01
xIn
0.01
Default
Description
-
Three-phase currents
0=False
Block signal for all bi-
nary outputs
Description
High alarm
High warning
Low warning
Low alarm
Phase A current instantane-
ous value amplitude in am-
peres
Phase B current instantane-
ous value amplitude in am-
peres
Phase C current instantane-
ous value amplitude in am-
peres
Demand value of IL1 current
Demand value of IL2 current
Demand value of IL3 current
Default
1=on
1=1 out of 3
1.40
1.20
0.00
1MRS759142 F
Description
Operation Off / On
Number of phases
required by limit
supervision
High alarm current
limit
High warning cur-
rent limit
Low warning cur-
rent limit
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents