ABB RELION REX640 Technical Manual page 1465

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Name
Type
I_ANGL_RES
FLOAT32
I_DB_RES
FLOAT32
I_DMD_RES
FLOAT32
I_RANGE_RES
Enum
Max demand Io
FLOAT32
Min demand Io
FLOAT32
Time max demand Io
Timestamp
Time min demand Io
Timestamp
8.1.8.8
Technical data
Table 1399: RESCMMXU Technical data
Characteristic
Operation accuracy
Suppression of harmonics
8.1.9
Residual voltage measurement RESVMMXU (ANSI VG/VN)
8.1.9.1
Identification
Function description
Residual voltage measurement
8.1.9.2
Function block
Figure 811: Function block
REX640
Technical Manual
Values (Range)
Unit
-180.00...180.00
deg
0.00...40.00
xIn
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...40.00
xIn
0.00...40.00
xIn
Value
At the frequency f = f
±0.5 % or ±0.002 × I
(at currents in the range of 0.01...4.00 × I
DFT: -50 dB at f = n × f
RMS: No suppression
IEC 61850
identification
RESVMMXU
Measurement functions
Description
Residual current angle
Residual current Ampli-
tude, magnitude of
deadband value
Demand value of resid-
ual current
Residual current Ampli-
tude range
Maximum demand for
residual current
Minimum demand for
residual current
Time of maximum de-
mand residual current
Time of minimum de-
mand residual current
n
n
, where n = 2, 3, 4, 5,...
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
Uo
VG/VN
)
n
1465