ABB RELION REX640 Technical Manual page 1351

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 1299: MSVPR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
0.05...1.20
Operate delay time
100...300000
Voltage selection
1=phase-to-earth
2=phase-to-phase
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Phase supervision
1=A or AB
2=B or BC
4=C or CA
7=A&B&C or
AB&BC&CA
Table 1300: MSVPR Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
6.8.9
MSVPR Monitored data
Table 1301: MSVPR Monitored data
Name
Type
U_AMPL_A
FLOAT32
U_AMPL_B
FLOAT32
U_AMPL_C
FLOAT32
U_AMPL_AB
FLOAT32
U_AMPL_BC
FLOAT32
U_AMPL_CA
FLOAT32
MSVPR
Enum
REX640
Technical Manual
Unit
Step
xUn
0.01
ms
100
Unit
Step
ms
1
Values (Range)
0.00...5.00
0.00...5.00
0.00...5.00
0.00...5.00
0.00...5.00
0.00...5.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Supervision functions
Default
1=on
0.25
100
2=phase-to-phase
3=3 out of 3
7=A&B&C or
AB&BC&CA
Default
20
Unit
Description
xUn
Remanent voltage of
phase A
xUn
Remanent voltage of
phase B
xUn
Remanent voltage of
phase C
xUn
Remanent voltage of
phase to phase AB
xUn
Remanent voltage of
phase to phase BC
xUn
Remanent voltage of
phase to phase CA
Status
Description
Operation Off / On
Start value
Operate delay time
Parameter to select
phase or phase-to-
phase voltages
Number of phases
required for voltage
supervision
Monitored voltage
phase
Description
Reset delay time
1351