ABB RELION REX640 Technical Manual page 1250

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
Name
CRL
LCG
5.10.7
DSOCPSCH Settings
Table 1185: DSOCPSCH Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Scheme type
1=None
2=Intertrip
3=Permissive Un-
derreach
4=Permissive Over-
reach
5=Blocking
Carrier Min Dur
0...60000
Coordination Time
0...60000
Table 1186: DSOCPSCH Non group settings (Advanced)
Parameter
Values (Range)
Unblock Mode
1=Off
2=Permanent
3=Time window
Loss of carrier time 0...60000
5.10.8
DSOCPSCH Monitored data
Table 1187: DSOCPSCH Monitored data
Name
Type
DSOCPSCH
Enum
1250
Type
BOOLEAN
BOOLEAN
Unit
Step
ms
1
ms
1
Unit
Step
ms
1
Values (Range)
1=on
2=blocked
3=test
4=test/blocked
5=off
Description
Carrier received after unblock
logic
Loss of guard
Default
1=on
3=Permissive Un-
derreach
100
35
Default
1=Off
35
Unit
Description
Status
1MRS759142 F
Description
Operation Off / On
Scheme type, mode
of operation
Minimum duration
of a carrier send
signal
Co-ordination tim-
er for blocking
scheme
Description
Operation mode of
unblocking logic
Pickup security
timer on loss of
carrier guard signal
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents