Protection related functions
5.12.4
Analog channel configuration
CRWPSCH has one analog group input which must be properly configured.
Table 1197: Analog inputs
Input
U3P
There are a few special conditions which must be noted with the configuration.
Table 1198: Special conditions
Condition
U3P connected to real meas-
urements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
5.12.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "on" and "off".
The operation of CRWPSCH can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
1266
Description
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
Description
The function can work with any two phases connected but it
is recommended to connect all three voltage channels.
1MRS759142 F
Operation setting. The
Technical Manual