ABB RELION REX640 Technical Manual page 1284

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
below the minimum level before
state is activated. If the drop-off continues for more than
deactivated.
Blocking logic
The binary input BLOCK can be used to block the function. The activation of the
BLOCK input deactivates the RELEASE output and resets Timer.
5.14.6
Application
The three-phase power directional element function DPSRDIR improves the
possibility to obtain a selective function of the overcurrent protection in meshed
networks. DPSRDIR is used to block or release other overcurrent protection
functions.
5.14.7
Signals
5.14.7.1
DPSRDIR Input signals
Table 1213: DPSRDIR Input signals
Name
I3P
U3P
BLOCK
5.14.7.2
DPSRDIR Output signals
Table 1214: DPSRDIR Output signals
Name
RELEASE
DIRECTION
5.14.8
DPSRDIR Settings
Table 1215: DPSRDIR Group settings (Basic)
Parameter
Values (Range)
Release delay time
0...1000
Characteristic an-
-179...180
gle
Table continues on the next page
1284
Release delay time is exceeded, the Timer reset
Type
SIGNAL
SIGNAL
BOOLEAN
Type
BOOLEAN
Enum
Unit
Step
ms
1
deg
1
Reset delay time , Timer is
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
Description
Release signal if direction cri-
teria is satisified
Direction information
Default
10
60
1MRS759142 F
Description
Release delay time
Characteristic an-
gle
REX640
Technical Manual