Measurement functions
Measurement mode setting
values
PhsA
PhsB
PhsC
Depending upon the set
module calculates active power, reactive power and apparent power values from the
available set of measurements.
P
= Re( )
Q
= Im( )
S
=
Cos
The calculated powers are available as function outputs S_INST, P_INST, Q_INST
and the power factor angle as PF_INST.
Depending on the unit multiplier selected with
power values in the monitored data and measurement view are presented in units of
kVA/kW/kVAr or in units of MVA/MW/MVAr.
1440
Measurement mode , the Power and energy calculation
S
S
2
2
S
P
Q
=
+
P
ϕ =
S
Power calculation
*
S
3
U I
A
A
= ⋅
*
S
U I
3
B
B
= ⋅
*
S
3
U I
C
C
= ⋅
Power unit Mult , the calculated
1MRS759142 F
(Equation 345)
(Equation 346)
(Equation 347)
(Equation 348)
(Equation 349)
(Equation 350)
(Equation 351)
REX640
Technical Manual