ABB RELION REX640 Technical Manual page 1489

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
that fit into the available recording memory. This information can be seen with
the Rem. amount of rec. monitored data. The fixed memory size allocated to the
recorder can fit in two recordings that are ten seconds long. The recordings contain
data from all analog and binary channels of the disturbance recorder, at the sample
rate of 32 samples per fundamental cycle.
The number of recordings in the memory can be viewed with the Number of
recordings monitored data. The used memory space can be viewed with the Rec.
memory used monitored data. It is shown as a percentage value.
8.2.3.4
Sampling frequencies
The sampling frequency of the disturbance recorder analog channels depends
on the set rated frequency. One fundamental cycle always contains the number
of samples set with the
channels are sampled once per task execution of the disturbance recorder, the
sampling frequency of binary channels is 400 Hz at the rated frequency of 50 Hz and
480 Hz at the rated frequency of 60 Hz.
Table 1437: Sampling frequencies of the disturbance recorder analog and binary
channels
Storage rate
(samples per
fundamental
cycle)
32
16
8
8.2.3.5
Uploading of recordings
The protection relay stores COMTRADE files to the C:\COMTRADE folder. The files
can be uploaded with PCM600 or any appropriate computer software that can
access the C:\COMTRADE folder.
One complete disturbance recording consists of two COMTRADE file types: the
configuration file and the data file. The file name is the same for both file types. The
configuration file has .CFG and the data file .DAT as the file extension.
REX640
Technical Manual
The maximum number of recordings is 100.
Storage rate parameter. Since the states of the binary
Recording
Rated frequency = 50 Hz
length
Sampling
frequency of
analog
channels
1 · Record
1600 Hz
length
2 · Record
800 Hz
length
4 · Record
400 Hz
length
Measurement functions
Rated frequency = 60 Hz
Sampling
Sampling
frequency of
frequency of
binary
analog
channels
channels
400 Hz
1920 Hz
400 Hz
960 Hz
400 Hz
480 Hz
Sampling
frequency of
binary
channels
480 Hz
480 Hz
480 Hz
1489

Advertisement

Table of Contents
loading

Table of Contents