Protection functions
exceeds the set limit. The operation time characteristics can be selected to be
either definite time (DT) or inverse definite minimum time (IDMT). The operation
under alarm stage is either based on the DT characteristics or the faulty element
counter of a capacitor bank.
CUBPTOC has a blocking functionality. It is possible to block the function outputs,
timers or the function itself.
4.12.2.4
Analog channel configuration
CUBPTOC has two analog group inputs which must be properly configured.
Table 1064: Analog inputs
Input
IUNB
I3P
There are a few special conditions which must be noted with the configuration.
Table 1065: Special conditions
Condition
IUNB measurement
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.12.2.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off". The current unbalance
protection for shunt capacitor banks operates on the DFT measurement mode.
The operation of CUBPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
1120
Description
Unbalance current (measured)
Three-phase currents
See the preprocessing function blocks in this document for the possible
signal sources.
Description
The function requires that the unbalance current measure-
ment is connected via the RESTCTR function block.
1MRS759142 F
Operation setting. The
Technical Manual
REX640