Protection functions
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.8.2.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of DOPPDPR can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
BLOCK
Figure 593: Functional module diagram
Power calculation
This module calculates the apparent power based on the selected voltages and
currents. The
are used. It is also possible to use positive-sequence components for calculating the
apparent power which makes the determination of power insensitive to a possible
asymmetry in currents or voltages and corresponds to the real load on the prime
mover of the generator.
Table 1001: Power calculation
Measurement mode setting
PhsA, PhsB, PhsC
Arone
Table continues on the next page
1064
I_A
I_B
I3P
I_C
I
1
U_AB
U_BC
U3P
U_CA
U
1
Measurement mode setting determines which voltages and currents
Level
detector
Power
calculation
Directional
calculation
Power calculation
.
S
U
I
a
( )
P
Re
=
S
U
=
ab
( )
P
Re
=
1MRS759142 F
Operation setting. The
Timer
OPERATE
t
.
.
*
*
*
U
I
U
I

a
b
b
c
c
S
*
*
I
U
I
a
bc
c
S
Technical Manual