ABB RELION REX640 Technical Manual page 1116

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Blocking mode which selects the blocking mode. The BLOCK input can be controlled
by a binary input, a horizontal communication input or an internal signal of
the protection relay's program. The influence of the BLOCK signal activation is
preselected with the global setting
The
mode, the operation timer is frozen to the prevailing value. In the "Block all" mode,
the whole function is blocked and the timers are reset. In the "Block OPERATE
output" mode, COLPTOC is executed normally but the OPR_OVLOD and OPR_UN_I
outputs are not allowed to activate.
4.12.1.6
Application
The application area for three-phase overload protection function of shunt
capacitor bank is the protection of power capacitor banks intended for reactive
power compensation and filtering of the harmonics. Shunt capacitor banks provide
a low-impedance path to harmonic currents and hence attract harmonic currents
flowing in the system. Increased harmonic currents result in excessive voltage stress
across the capacitor bank. According to the standards, a high-voltage capacitor
shall be able to withstand 10% overload. Loading beyond that can cause damage
to the capacitor bank and in turn to the system. Hence, COLPTOC is specially
designed for the protection against overloads produced by harmonic currents and
overvoltage.
Undercurrent protection is used to disconnect the capacitor bank from the rest
of the power system when the voltage at the capacitor bank terminals is too
low for too long a period of time. To avoid an undercurrent trip operation when
the capacitor bank is disconnected from the power system, the undercurrent
functionality is blocked by using the capacitor bank circuit breaker status signal.
Furthermore, the reclosing inhibition feature provides protection against the
reconnection of a charged capacitor to a live network. Whenever the capacitor
bank circuit breaker is opened, the reclosing is inhibited for the duration of
the discharge time of the capacitor. The reclosing inhibition functionality can be
disabled manually or automatically. In the manual mode, the inhibition reclosing
has to be manually reset and in automatic mode, the reclosing inhibitionl resets
automatically after the set time.
4.12.1.7
Signals
1116
Blocking mode setting has three blocking methods. In the "Freeze timers"
The BLOCK input does not block the BLK_CLOSE signal.
Blocking mode .
1MRS759142 F
REX640
Technical Manual