8.1.12.8
Technical data
Table 1428: VSMSQI Technical data
Characteristic
Operation accuracy
Suppression of harmonics
8.1.13
Three-phase power and energy measurement PEMMXU
(ANSI P, E)
8.1.13.1
Identification
Function description
Three-phase power and energy
measurement
8.1.13.2
Function block
Figure 815: Function block
8.1.13.3
Functionality
The three-phase power and energy measurement function PEMMXU calculates
energy and power from the available current and voltage inputs. The function stores
the accumulated values of the real and reactive energy in both directions, and
presents these values as numerical and pulse outputs.
REX640
Technical Manual
Values (Range)
Unit
2=low
3=high-high
4=low-low
Value
Depending on the frequency of the voltage
measured: f
At voltages in range 0.01...1.15 × U
±1.0 % or ±0.002 × U
DFT: -50 dB at f = n × f
IEC 61850
identification
PEMMXU
Measurement functions
Description
±2 Hz
n
n
, where n = 2, 3, 4, 5,...
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
P, E
P, E
n
1481