ABB RELION REX640 Technical Manual page 1382

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Condition monitoring functions
Table 1319: ESDCSSWI Non group settings (Advanced)
Parameter
Values (Range)
Counter initial Val
0...99999
Ini inactive days
0...9999
Inactive Alm hours
0...23
7.2.8
ESDCSSWI Monitored data
Table 1320: ESDCSSWI Monitored data
Name
Type
T_TRV_OP
FLOAT32
T_TRV_CL
FLOAT32
T_TRV_MAX_OP
FLOAT32
T_TRV_MAX_CL
FLOAT32
NO_OPR
INT32
INA_DAYS
INT32
ESDCSSWI
Enum
7.2.9
Technical data
Table 1321: ESDCSSWI technical data
Characteristic
Operate time accuracy
Travelling time measurement
7.3
Hot-spot and insulation ageing rate monitoring for
transformers HSARSPTR (ANSI 26/49HS)
1382
Unit
Step
1
1
h
1
Values (Range)
0...60000
0...60000
0...60000
0...60000
0...99999
0...9999
1=on
2=blocked
3=test
4=test/blocked
5=off
Default
0
0
0
Unit
ms
ms
ms
ms
Value
±1.0 % of the set value or ±20 ms
 +10 ms / -5 ms
1MRS759142 F
Description
Operation numbers
counter initializa-
tion
Initial value of the
inactive days coun-
ter
Alarm time of the
inactive days coun-
ter in hours
Description
Travel time of the
switch during opening
operation
Travel time of the
switch during closing
operation
Maximum travel time
during opening opera-
tion
Maximum travel time
during closing opera-
tion
Number of switch oper-
ation cycle
The number of days
switch has been inac-
tive
Status
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents