Protection functions
4.9.4
Analog channel configuration
ARCSARC has two analog group inputs which must be properly configured.
Table 1027: Analog inputs
Input
I3P
IRES
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.9.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of ARCSARC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
OPR_MODE
REM_FLT_ARC
Figure 609: Functional module diagram
Level detector 1
The measured phase currents are compared phasewise to the set
If the measured value exceeds the set
the exceeding of the value to the operation mode selector.
1
Can be connected to GRPOFF if "Light only" or "BI controlled" operation modes are used
1086
1
1
See the preprocessing function blocks in this document for the possible
signal sources. The GRPOFF signal is available in the function block called
Protection.
I_A
I_B
I3P
I_C
Io
IRES
BLOCK
Description
Three-phase currents, necessary when the operation mode
"Light +current" is used
Residual current (measured or calculated)
Level
Operation
detector
mode
1
selector
Level
detector
2
ARC light
detection
Phase start value , the level detector reports
1MRS759142 F
Operation setting. The
Fixed delay 1
OPERATE
t
Fixed delay 2
ARC_FLT_DET
t
ALARM
Supervision
Phase start value .
Technical Manual
REX640