Protection functions
Table 940: OOSRPSB Group settings (Advanced)
Parameter
Values (Range)
Zone 1 reach
1...100
Max number slips
1...10
Max Num slips Zn2
1...20
Max Num slips Zn3
1...20
Operate delay time
20...60000
Operate dropout
20...60000
time
V dip time
500...5000
Zone 2 enable
1=Yes
0=No
Zone 3 enable
1=Yes
0=No
Table 941: OOSRPSB Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 942: OOSRPSB Non group settings (Advanced)
Parameter
Values (Range)
Min Ps Seq current
0.01...10.00
Max Ng Seq current 0.01...10.00
Breaker open time
0...300
Disable time
20...60000
Reset time
20...60000
Voltage reversal
0=No
1=Yes
1014
Unit
Step
%
1
1
1
1
ms
10
ms
10
ms
10
Unit
Step
Unit
Step
xIn
0.01
xIn
0.01
ms
1
ms
10
ms
10
1MRS759142 F
Default
Description
70
Percent of Mho for-
ward reach indicat-
ing the end of zone
1 and the beginning
of zone 2
1
Number of pole
slips before operat-
ing zone 1
1
Number of pole
slips before operat-
ing zone 2
1
Number of pole
slips before operat-
ing zone 3
300
Delay after OOS op-
erate detected
100
Time operate out-
put remains active
2000
Maximum allowable
time for voltage to
dip
0=No
Enable zone 2 fea-
ture
0=No
Enable zone 3 fea-
ture
Default
Description
1=on
Operation Off / On
Default
Description
0.10
Minimum positive
sequence current
for operation
0.20
Maximum negative
sequence current
for operation
30
Opening time of
the breaker
5000
Additional time
function is disabled
after removal of
DISABLE input
5000
Time to reset
OOS condition and
counters
0=No
Rotate voltage sig-
nals by 180 degrees
Technical Manual
REX640

Advertisement

Table of Contents
loading