Protection related functions
5.3.6
Signals
5.3.6.1
TRPPTRC Input signals
Table 1124: TRPPTRC Input signals
Name
BLOCK
OPERATE
RST_LKOUT
5.3.6.2
TRPPTRC Output signals
Table 1125: TRPPTRC Output signals
Name
TRIP
CL_LKOUT
5.3.7
TRPPTRC Settings
Table 1126: TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Trip pulse time
20...60000
Trip output mode
1=Non-latched
2=Latched
3=Lockout
5.3.8
TRPPTRC Monitored data
Table 1127: TRPPTRC Monitored data
Name
Type
TRPPTRC
Enum
1178
Type
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
ms
1
Values (Range)
1=on
2=blocked
3=test
4=test/blocked
5=off
Default
Description
0=False
Block of function
0=False
Operate
0=False
Input for resetting
the circuit breaker
lockout function
Description
General trip output signal
Circuit breaker lockout out-
put (set until reset)
Default
1=on
250
1=Non-latched
Unit
1MRS759142 F
Description
Operation Off / On
Minimum duration
of trip output sig-
nal
Select the opera-
tion mode for trip
output
Description
Status
REX640
Technical Manual

Advertisement

Table of Contents
loading