Figure 785: Functional module diagram
7.2.4.1
Switch status
This module monitors the position of the earthing switch or disconnector, that is,
whether the switch is in an open, closed, intermediate or faulty position.
The OPENPOS output is activated when the auxiliary input contact POSCLOSE input is
FALSE and the POSOPEN input is TRUE. The CLOSEPOS output is activated when the
POSOPEN input is FALSE and the
The INVALIDPOS output is activated when both auxiliary contacts have the same
value, that is, both are in the same logical level.
7.2.4.2
Inactivity monitoring
The purpose of the inactivity monitoring is to indicate if the earthing switch or
disconnector has not been operated for a long time.
This module calculates the number of days the earthing switch or disconnector has
remained inactive, that is, has stayed in the same open, closed and intermediate
or faulty state. The calculation is done by monitoring the states of the POSOPEN,
POSCLOSE auxiliary contacts. The inactive days INA_DAYS is available in the
monitored data view. For relay retrofit installations, it is possible to initialize
REX640
Technical Manual
POSCLOSE
POSOPEN
CLOSE_EXE
OPEN_EXE
RST_TRV_T
BLOCK
Switch
status
Inactivity
monitoring
Operation
counter
TRV_T_OP_ALM
Contact
travel time
TRV_T_CL_ALM
POSCLOSE input is TRUE.
Condition monitoring functions
OPENPOS
CLOSEPOS
INVALIDPOS
MON_ALM
OPR_ALM
OPR_LO