Protection functions
When the measured current value is used for start-up supervision in the "IIt" and
"IIt & stall" modes, the module initially recognizes the de-energized condition of the
motor when the values of all three phase currents are less than
for longer than 100 milliseconds. If any of the phase currents of the de-energized
condition rises to a value equal to or greater than
output signal is activated indicating that the motor start-up is in progress. The
MOT_START output remains active until the values of all three phase currents drop
below 90 percent of the set value of
for a time of
Figure 615: Functionality of start-up supervision in the "IIt and IIt&stall" mode
In case of the "IIt, CB" or "IIt & stall, CB" modes, the function initially recognizes the
de-energized condition of the motor when the value of all three phase currents is
below the value of the
of the motor start-up is recognized when CB is closed, that is, when the CB_CLOSED
input is activated and at least one phase current value exceeds the
A setting.
These two events do not take place at the same instant, that is, the CB main
contact is closed first, in which case the phase current value rises above 0.1 pu and
after some delay the CB auxiliary contact gives the information of the CB_CLOSED
input. In some cases, the CB_CLOSED input can be active but the value of current
may not be greater than the value of the
both possibilities, a time slot of 200 milliseconds is provided for current and the
CB_CLOSED input. If both events occur during this time, the motor start-up is
recognized.
The motor start-up ends either within the value of the
setting from the beginning of the start-up or the opening of CB or when the
CB_CLOSED input is deactivated. The operation of the MOT_START output signal in
this operation mode is as illustrated in
This CB mode can be used in soft-started or slip ring motors for protection against
a high starting current, that is, a problem in starting and so on.
1096
Str over delay time , that is, until the start-up situation is over.
Motor standstill A setting for 100 milliseconds. The beginning
Start detection A , the MOT_START
Start detection A and remain below that level
Motor standstill A setting. To allow
Str over delay time
Figure 616
.
1MRS759142 F
Motor standstill A
Motor standstill