ABB RELION REX640 Technical Manual page 1029

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
The current measurement of the function is based on two alternative measurement
modes, "DFT" and "Peak-To-Peak". The measurement mode is selected using the
Measurement mode setting.
If the current magnitude is below 0.02 · I
the impedance value is not evaluated and the maximum impedance value (99.999
pu) is shown in the Monitored data view.
The calculated phase-phase impedance amplitudes Z_AMPL_AB, Z_AMPL_BC and
Z_AMPL_CA are available as pu values in the Monitored data view.
Underimpedance detection
The operating characteristic is an origin-centric circle on the impedance plane. The
origin-centric circular characteristic is defined using the
calculated impedance value enters the circle in the impedance plane, the module
sends an enabling signal to start the Timer.
Figure 571: Origin-centric circular operating characteristics
Separate zones with an offset-mho characteristic can be designed using multiple
instances of the UZPDIS function with
with
the distance of the top of the circle from R-axis. If the sign of the
the top of the circle is above the R-axis and if it is negative, the top of the circle
will be below the R-axis.
circle is displaced from the X-axis. If the sign of the
REX640
Technical Manual
The calculated impedances are converted to a pu impedance as the
operating characteristics are defined using the
%Zb.
Offset and Displacement setting values as shown in Figure
Displacement is the distance by which the center of the
, where I
is the nominal phase current,
N
N
Polar reach setting in
Polar reach setting. If the
Offset enable setting and parameterized
Displacement setting is positive,
Protection functions
Figure 572
Offset is
.
Offset is positive,
1029